Products » Level Sensors » Flowline EchoPod UG01 & UG03 Reflective Ultrasonic Level Transmitters
Flowline EchoPod UG01 & UG03 Reflective Ultrasonic Level Transmitters
Reliable and Accurate Level Measurement for Small Tanks
The Flowline EchoPod UG01 and UG03 reflective ultrasonic level transmitters offer continuous level measurement up to 9.8 feet (3 meters). These versatile devices provide a 4-20mA analog signal output along with four configurable relays, making them ideal for a wide range of applications including day tanks, cooling towers, and process sumps. The UG01 and UG03 are particularly suited for small tanks and challenging environments with non-foaming or highly vaporous media, thanks to their proprietary Reflective Technology™ which ensures reliable operation even in condensing conditions.
The transmitters feature WebCal software for easy setup and monitoring, allowing users to configure fail-safes, alarms, and pump control functionality. With rugged PVDF construction, they are engineered for durability and reliable performance in a variety of industrial applications such as chemical, water, wastewater, and oil processing.
-
Overview
-
Ordering Information
-
Specification
-
Literature
The Flowline EchoPod UG01 and UG03 ultrasonic level transmitters offer reliable and accurate level measurement for small tanks. With versatile applications, these sensors are designed for use in a wide range of industrial processes. The UG01 and UG03 are engineered with innovative features that ensure ease of use, precision, and durability, especially in condensing or vaporous environments.
Key Features:
- Available in 1.5m (4.9’) and 3m (9.8’) measurement ranges.
- Fail-safe diagnostics with selectable relay and signal outputs.
- Narrow 2” (5cm) beam width for optimized use in smaller tanks.
- Corrosion-resistant PVDF transducer and compact polypropylene enclosure.
- Short 1.5” (3.8cm) dead band maximizes tank filling capacity.
- Automatic temperature compensation for accuracy from -40° to 80°C.
- Four programmable relays with embedded level control logic:
- 1 pump or valve with 3 alarms.
- 2 pumps lead-lag with 2 alarms.
- 2 pumps duplexing with 2 alarms.
- 4 independent switch point alarms.
Ordering Information for Flowline EchoPod UG0 Series
Select the appropriate options to build the model number for the Flowline EchoPod UG0 series. Example model number: UG0-01-1-4
Parameter | Option | Description |
---|---|---|
Sensor Range | 1 | 1.5m (4.9 ft) |
3 | 3m (9.8 ft) | |
Process Mount | 0 | 2″ NPT |
1 | 2″ G | |
FOB USB Adapter | 0 | Without FOB |
1 | With FOB | |
Example Model Number | UG0-01-1-4 (3m range, 2″ NPT, with FOB) |
Specifications
Specification | UG01 | UG03 |
---|---|---|
Range | 1.5″ to 4.9″ (3.8 cm to 1.5 m) | 4″ to 9.8″ (10.1 cm to 3 m) |
Accuracy | ±0.125″ (3 mm) | ±0.2% of range |
Resolution | 0.019″ (0.5 mm) | 0.039″ (1 mm) |
Dead Band | 1.5″ (3.8 cm) | 4″ (10.1 cm) |
Beam Width | 2″ (5 cm) | |
Configuration | WebCal™ PC Windows® USB® 2.0 | |
Memory | Non-volatile | |
Supply Voltage | 14-28 VDC | |
Max. Consumption | 0.5 W | |
Loop Resistance | 500 ohms @ 24 VDC | |
Signal Output | 4-20mA, two-wire | |
Signal Invert | 4-20mA or 20-4mA | |
Signal Fail-Safe | 4mA, 20mA, 21mA, 22mA, hold last | |
Contact Type | (4) SPST relays | |
Contact Rating | 60 VA, 1A max | |
Contact Fail-Safe | Open, close, hold last | |
Process Temp. | F: -40° to 176° | C: -40° to 80° |
Ambient Temp. | F: -31° to 140° | C: -35° to 60° |
Pressure | 30 psi (2 bar) | |
Enclosure Rating | Type 6P (IP68) | |
Enclosure Material | Polypropylene | |
Transducer Material | Polyvinylidene Fluoride | |
Cable Jacket Material | Polyurethane | |
Cable Type | 9-conductor, shielded | |
Cable Length | 48″ (1.2m) | |
Process Mount | UG01: 2” NPT, UG03: 2” G | |
Mount Gasket | Viton® | |
Classification | General Purpose | |
Approvals | UL 61010-1, CE, RoHS |