Flowline EchoPod UG01 & UG03 Reflective Ultrasonic Level Transmitters

Reliable and Accurate Level Measurement for Small Tanks

The Flowline EchoPod UG01 and UG03 reflective ultrasonic level transmitters offer continuous level measurement up to 9.8 feet (3 meters). These versatile devices provide a 4-20mA analog signal output along with four configurable relays, making them ideal for a wide range of applications including day tanks, cooling towers, and process sumps. The UG01 and UG03 are particularly suited for small tanks and challenging environments with non-foaming or highly vaporous media, thanks to their proprietary Reflective Technology™ which ensures reliable operation even in condensing conditions.

The transmitters feature WebCal software for easy setup and monitoring, allowing users to configure fail-safes, alarms, and pump control functionality. With rugged PVDF construction, they are engineered for durability and reliable performance in a variety of industrial applications such as chemical, water, wastewater, and oil processing.

Flowline EchoPod UG01 & UG03 Reflective Ultrasonic Level Transmitters
Flowline EchoPod UG01

The Flowline EchoPod UG01 and UG03 ultrasonic level transmitters offer reliable and accurate level measurement for small tanks. With versatile applications, these sensors are designed for use in a wide range of industrial processes. The UG01 and UG03 are engineered with innovative features that ensure ease of use, precision, and durability, especially in condensing or vaporous environments.

Key Features:

  • Available in 1.5m (4.9’) and 3m (9.8’) measurement ranges.
  • Fail-safe diagnostics with selectable relay and signal outputs.
  • Narrow 2” (5cm) beam width for optimized use in smaller tanks.
  • Corrosion-resistant PVDF transducer and compact polypropylene enclosure.
  • Short 1.5” (3.8cm) dead band maximizes tank filling capacity.
  • Automatic temperature compensation for accuracy from -40° to 80°C.
  • Four programmable relays with embedded level control logic:
    • 1 pump or valve with 3 alarms.
    • 2 pumps lead-lag with 2 alarms.
    • 2 pumps duplexing with 2 alarms.
    • 4 independent switch point alarms.

Ordering Information for Flowline EchoPod UG0 Series

Select the appropriate options to build the model number for the Flowline EchoPod UG0 series. Example model number: UG0-01-1-4

ParameterOptionDescription
Sensor Range11.5m (4.9 ft)
33m (9.8 ft)
Process Mount02″ NPT
12″ G
FOB USB Adapter0Without FOB
1With FOB
Example Model NumberUG0-01-1-4 (3m range, 2″ NPT, with FOB)

Specifications

Specification UG01 UG03
Range 1.5″ to 4.9″ (3.8 cm to 1.5 m) 4″ to 9.8″ (10.1 cm to 3 m)
Accuracy ±0.125″ (3 mm) ±0.2% of range
Resolution 0.019″ (0.5 mm) 0.039″ (1 mm)
Dead Band 1.5″ (3.8 cm) 4″ (10.1 cm)
Beam Width 2″ (5 cm)
Configuration WebCal™ PC Windows® USB® 2.0
Memory Non-volatile
Supply Voltage 14-28 VDC
Max. Consumption 0.5 W
Loop Resistance 500 ohms @ 24 VDC
Signal Output 4-20mA, two-wire
Signal Invert 4-20mA or 20-4mA
Signal Fail-Safe 4mA, 20mA, 21mA, 22mA, hold last
Contact Type (4) SPST relays
Contact Rating 60 VA, 1A max
Contact Fail-Safe Open, close, hold last
Process Temp. F: -40° to 176° C: -40° to 80°
Ambient Temp. F: -31° to 140° C: -35° to 60°
Pressure 30 psi (2 bar)
Enclosure Rating Type 6P (IP68)
Enclosure Material Polypropylene
Transducer Material Polyvinylidene Fluoride
Cable Jacket Material Polyurethane
Cable Type 9-conductor, shielded
Cable Length 48″ (1.2m)
Process Mount UG01: 2” NPT, UG03: 2” G
Mount Gasket Viton®
Classification General Purpose
Approvals UL 61010-1, CE, RoHS